Description
Structure
- Vertical structure
- Two removable panel for easy maintenance
- Zinc-plated steel base, polyester powder RAL9005 orange peel finished
- Panels zinc-plated steel, polyester powder RAL7035 orange peel finished
- Base with mounting hole for wheels kit
- Arranged for lifting with lift truck
Refrigerant Circuit
- Single circuit air condensed
- Hermetic reciprocating compressor mod. 35
- Hermetic scroll compressor mod. 45…D8
- Ecological refrigerant gas R134A mod. 35…45
- Ecological refrigerant gas R407C mod. 58…D8
- Condenser with aluminium fins
- Evaporator mod. 35…A3 : immersed coil
- Evaporator mod. A6…D8 : stainless steel plate
- Expansion capillary pipe mod. 35…70
- Thermostatic Expansion valve mod. 85…D8
Hydraulic circuit
- Standard equipment with pump and tank
- Fluid: water and antifreeeze
- Non ferrous circuit on request mod. 35…85
- Non ferrous circuit std. mod. 95…D8
- Peripheral pump mod. 35…85
- Centrifugal pump mod. 95…D8
- Fixed by-pass with manometer mod. 35…A6
- Adjustable by-pass with manometer mod. A8…D8
- Electrical level indicator on request mod. 35…85
- Electrical level indicator std. mod. 95…D8
Electrical Circuit
- Electrical panel for indoor installations mod. 35…85
- Electrical panel for outdoor installations mod. 95…D8
- Control panel with general switch and alarms diagnosis
- Electronic thermostat with temperature precision +/-2K
- Power supply and signals on terminals
- Standard signals: general alarm, on-off remote control
- Signals on request: electrical level, flow switch, antifreeze protection
These units are chillers for process cooling that are not covered by the regulations for MT (Medium Temperature – EU 2015/1095) and HT (High Temperature – EU 2016/2281).
The working limits for the fluid temperature, are:
- base units: +13°C ÷ +25°C
- units for low water temperature: -5°C ÷ +1°C